Delta Electronics VFD-S manual Output Frequency, 8-00, 8-01, 8-02, 8-03

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 115
Image 115
8-00

Chapter 5 ParametersVFD-S Series

 

Group 8: Special Parameters

 

 

 

 

8-00

DC Brake Current Level

Unit: 1

 

Settings

d0 to d30%

Factory Setting: d0

 

 

 

 

This parameter determines the level of DC Brake Voltage Level output to the motor during start-up and stopping. When setting DC Brake Voltage, the Maximum Output Voltage (Pr.1-

02)is regarded as 100%. It is recommended to start with a low DC Brake Voltage Level and then increase until proper holding torque has been attained.

8-01

DC Brake Time during Start-up

Unit: 0.1

 

Settings

d0.0 to d60.0 sec

Factory Setting: d0.0

 

This parameter determines the duration of time that the DC Brake Current will be applied to

the motor during the AC drive start-up.

 

 

 

 

8-02

DC Brake Time during Stopping

Unit: 0.1

 

Settings

d0.0 to d60.0 sec

Factory Setting: d0.0

 

 

 

 

This parameter determines the duration of time that the DC brake voltage will be applied to the motor during stopping. If stopping with DC Brake is desired, then Pr.2-02 must be set to RAMP stop (d0).

8-03

Start-Point for DC Brake

Unit: 0.1

 

Settings

d0.0 to d400Hz

Factory Setting: d0.0

 

 

 

 

This parameter determines the frequency when DC Brake will begin during deceleration.

Output Frequency

01-05

Minimum Output Frequency

Operation

Start-Point for

DC Brake

Time during

Stopping

08-03

08-01

Time

Command

ON

OFF

8-018-028-03DC Brake Voltage %

08-02

5-58

Revision August 2008, SE09, SW V2.61

Page 115
Image 115
Delta Electronics VFD-S manual Output Frequency, 8-00, 8-01, 8-02, 8-03