Delta Electronics VFD-S manual Control Terminals, RJ11

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 40
Image 40
2.4.4 Control Terminals

Chapter 2 Installation and WiringVFD-S Series

2.4.4 Control Terminals

Control Terminal Wiring (Factory Setting) A. XXXSXXA/B/D/U

+10V AVI AFM M0 M1 M2 M3 M4 M5 GND

RA

Relay contactor output

RB

RC

Factory setting : Fault indication

 

MO1

 

Operation freq. setting potentiometer VR : 3K~5K

Corrector potentiometer VR : 1K~5K

Freq. meter 0~10 VDC

Full scale voltmeter

RJ11 Multi-step speed 3 Multi-step speed 2

Multi-step speed 1 Reset

Reverse/Stop

Forward/Stop

MCM

Photo coupler output

Factory setting : in work

RJ11

RS485 Communication port

6 ~ 1

Wire Gauge: 24-12 AWG

Wire Type: Copper Only

Torque: 4 kgf-cm (3.5 in-lbf)

B. XXXSXXE

Manual background * Manual background * Manual backgroundManual backgroundManual backgroundManual background

Manual background Multi-step speed 3

Wire Gauge: 24-16 AWG

Wire Type: Copper Only

Torque: 2 kgf-cm (1.7 in-lbf)

Terminal symbols and functions

Terminal

Terminal Function

Factory Settings (NPN mode)

Symbol

ON: Connect to GND

 

M0

Multi-function auxiliary input

 

M1

Multi-function input 1

Refer to Pr.4-04 to Pr.4-08 for programming

M2

Multi-function input 2

the Multi-function Inputs.

M3

Multi-function input 3

ON: the activation current is 16mA.

M4

Multi-function input 4

OFF: leakage current tolerance is 10μA.

 

M5

Multi-function Input 5

 

+17V

DC Voltage Source

+17VDC, 20mA used for PNP mode.

GND

Digital Signal Common

Common for digital inputs and used for NPN

mode.

 

 

Revision August 2008, SE09, SW V2.61

2-25

Page 40
Image 40