2-05Loss of ACI Signal (4-20mA)

Chapter 5 ParametersVFD-S Series

2-05Loss of ACI Signal (4-20mA)

 

 

Factory Setting: d0

Settings

d0

Decelerate to 0 Hz

 

d1

Coast to stop and display “EF”

 

d2

Continue operation by last frequency command

 

 

 

This parameter is only effective when the Source of Frequency is commanded by a 4 to

20mA signal. The ACI input is considered lost when the ACI signal falls below 2mA.

2-06Analog Auxiliary Frequency Operation

Factory Setting: d0

Settings

d0

Disable

 

d1

Enable + AVI (0~10V)

 

d2

Enable + ACI (4~20mA)

 

 

 

This parameter is used to determinate that the analog signal to overlap is 0~10V (AVI) or

4~20mA (ACI).

To make sure the short PIN of J1 on the panel is correct position before setting this parameter.

5-30