Delta Electronics VFD-S manual RTU mode Command message

Models: VFD-S

1 185
Download 185 pages 61.91 Kb
Page 124
Image 124

Chapter 5 ParametersVFD-S Series

RTU mode:

Command message:

ADR

01H

CMD

03H

Starting data

21H

address

02H

Number of data

00H

(count by word)

02H

CRC CHK Low

6FH

CRC CHK High

F7H

Response message:

ADR

01H

CMD

03H

Number of data

04H

(count by byte)

 

Content of address

17H

2102H

70H

Content of address

00H

2103H

00H

CRC CHK Low

FEH

CRC CHK High

5CH

(2) 06H: single write, write single data to register.

Example: writing data 6000(1770H) to register 0100H. AMD address is 01H.

ASCII mode:

Command message:

 

STX

‘:’

 

ADR 1

‘0’

 

ADR 0

‘1’

 

CMD 1

‘0’

 

CMD 0

‘6’

 

 

‘0’

 

Data address

‘1’

 

‘0’

 

 

 

 

‘0’

 

 

‘1’

 

Data content

‘7’

 

‘7’

 

 

 

 

‘0’

 

LRC CHK 1

‘7’

 

LRC CHK 0

‘1’

 

END 1

CR

 

END 0

LF

RTU mode:

 

 

Command message:

 

 

ADR

01H

 

CMD

06H

 

Data address

01H

 

00H

 

 

 

Data content

17H

 

70H

 

 

 

CRC CHK Low

86H

 

CRC CHK High

22H

Response message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘0’

CMD 0

‘6’

 

‘0’

Data address

‘1’

‘0’

 

 

‘0’

 

‘1’

Data content

‘7’

‘7’

 

 

‘0’

LRC CHK 1

‘7’

LRC CHK 0

‘1’

END 1

CR

END 0

LF

Response message:

 

 

 

ADR

01H

CMD

06H

Data address

01H

00H

 

Data content

17H

70H

 

CRC CHK Low

86H

CRC CHK High

22H

Revision August 2008, SE09, SW V2.61

5-67

Page 124
Image 124
Delta Electronics VFD-S manual RTU mode Command message