Chapter 5 ParametersVFD-S Series

(3) Command code: 10H, write n word, n<=12

For example, writing 6000(1770H) to Pr 5-00 (address 0500H) and1000(03E8H) to Pr 5- 01 (address 0501H) with slave address 01H.

ASCII Mode:

Command message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD1

‘1’

CMD0

‘0’

Starting Data address

‘0’

 

‘5’

 

‘0’

 

‘0’

Number of data

‘0’

(count by word)

‘0’

 

‘0’

 

‘2’

Number of data

‘0’

(count by byte)

‘4’

Data content of

‘1’

address 0500H

 

‘7’

 

‘7’

 

‘0’

Data content of

‘0’

address 0501H

‘3’

 

‘E’

 

‘8’

LRC CHK 1

‘7

LRC CHK 0

‘2

END1

CR

END0

LF

Response message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD1

‘1’

CMD0

‘0’

Starting Data

‘0’

address

‘5’

 

‘0’

 

‘0’

Number of data

‘0’

(count by word)

‘0’

 

‘0’

 

‘2’

LRC CHK 1

‘E’

LRC CHK 0

‘8’

END1

CR

END0

LF

RTU mode:

Command message:

ADR

01H

CMD

10H

Starting Data address

05H

 

00H

Number of data

00H

(count by word)

02H

Number of data

04H

(count by Byte)

 

Data content of

17H

address 0500H

70H

Data content of

03H

address 0501H

E8H

CRC CHK Low

C8H

CRC CHK High

2EH

Response message:

ADR

01H

CMD

10H

Starting Data

05H

address

00H

Number of data

00H

(count by word)

02H

CRC CHK Low

41H

CRC CHK High

04H

5-68

Revision August 2008, SE09, SW V2.61

Page 125
Image 125
Delta Electronics VFD-S manual Command code 10H, write n word, n=12