IM584000300

Installation Instructions

Issue AB, April 3, 2013

Spec. No. 584000300 (Model 4015-X003)

 

 

CHAPTER 2.

INSTALLING THE SYSTEM

The individual components of the DC Power System may be shipped as a complete solution factory installed and wired in an IT rack, or may be shipped separately to be installed in a customer provided IT rack.

GENERAL REQUIREMENTS

This product is intended only for installation in a restricted access location on or above a non-combustible surface.

Front and rear access is required for installation.

Required minimum spacing from the rear of the power and control sub-rack to a wall or other solid surface is thirty-six (36) inches for proper ventilation of system components. Required minimum spacing from the rear of the load distribution sub- rack to a wall or other solid surface is twelve (12) inches for proper ventilation of system components.

See Figure 2-1for an air flow diagram.

Hot Aisle

Cold Aisle

Air Flow

Notes:

 

1. Do not block

 

air intake openings.

Front

Figure 2-1

Air Flow Diagram

Page 8

Chapter 2. Installing the System