IM584000300 Installation Instructions

Issue AB, April 3, 2013 Spec. No. 584000300 (Model 4015-X003)

Page 22 Chapter 3. Making Electrical Connections

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Figure 3-6

Sub-Rack Interconnections

LoadDistribution Sub-Rack DC Input Cables
(Factoryconnected in load distribution sub-rack,
customerto route into power and control
sub-rackand connect to power and control
sub-rackDC output terminals.)
BatteryTray Output Cables
(Factoryconnected in battery tray,
customerto route into power and
controlsub-rack and connect to
powerand control sub-rack battery
terminals.)
Rear

Load

Distribution

Sub-Rack

Power and

Control

Sub-Rack

Battery

Tray

*Note:Battery cables can also be
routedthrough the bottom of the
powerand control sub-rack.
BatteryTerminals
for400V DC Battery Strings
(fivesets of 1/4-20 x 5/8
studson 5/8centers for
doublehole lugs,
eachpolarity)
RearView
(coversremoved)
Negative
Battery* Positive
Battery*
++--
(Recommended
Torque:84 in-lbs
[9Nm])

Power and

Control

Sub-Rack
(Recommended
Torque:84 in-lbs
[9Nm])
400VDC Output Terminals
(twosets of 1/4-20 x 5/8
studson 5/8centers for
doublehole lugs,
eachpolarity)
Negative
Output Positive
Output