IM584000300

Installation Instructions

Issue AB, April 3, 2013

Spec. No. 584000300 (Model 4015-X003)

 

 

CHAPTER 5.

INITIALLY STARTING THE SYSTEM

Caution: Performing various steps in the following procedures may cause a service interruption and/or result in the extension of alarms. Notify any appropriate personnel before starting these procedures. Also, notify personnel when these procedures are completed.

Note: Contact Emerson sales for startup assistance.

INITIAL STARTUP PREPARATION

Refer to Figure 5-1for circuit breaker locations.

Ensure that all blocks in the appropriate “Installation Acceptance Checklist” starting on page 6 have been checked (except the last one).

Ensure that a rectifier module or a blank cover panel is installed in all rectifier mounting positions.

Ensure the distribution row input circuit breaker is in the OFF position (if furnished).

Ensure each load distribution circuit breaker is in the OFF position.

Ensure each rectifier module AC input circuit breaker is in the OFF position.

Ensure each battery tray circuit breaker is in the OFF position.

Load Distribution

Circuit Breakers

Distribution Row Input Circuit Breaker (if furnished)

Load

Distribution

Sub-Rack

Power and

Control

Sub-Rack

Battery

Tray

Front

Rectifier Module

AC Input Circuit Breakers

Battery Tray

Circuit Breaker

Figure 5-1

Circuit Breaker Locations

Page 42

Chapter 5. Initially Starting the System

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Page 52
Image 52
Emerson 4015 installation instructions Initial Startup Preparation, Circuit Breaker Locations Initially Starting the System