Installation Instructions

IM584000300

Spec. No. 584000300 (Model 4015-X003)

Issue AB, April 3, 2013

 

 

Load Distribution Sub-Rack

Return Busbar (-Bus) Grounding Point (cover removed)

(NPG Configurations Only) Note: This connection can be made here or on the power and control sub-rack as shown below.

(Wire Size Capacity:

 

10 AWG to 4 AWG)

 

(Recomended Torque:

 

80 in-lbs [9 Nm])

Rear View

Caution: In the NPG Configuration,

this equipment will have (after installation)

a connection between the earthed conductor of the DC power supply circuit and the earthing conductor.

(Recommended Torque:

84 in-lbs [9 Nm])

Return Busbar (-Bus) Grounding Point

(NPG Configurations Only)

Note: This connection can be made here or on the distribution sub-rack (if furnished) as shown above.

(one set of 1/4-20 x 1/2” studs on 5/8” centers for double hole lugs)

Power and Control Sub-Rack

Rear View

(covers removed)

Figure 3-4

Return Busbar (-Bus) Grounding Connection (NPG Configurations Only)

Chapter 3. Making Electrical Connections

Page 19

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Page 29
Image 29
Emerson 4015 installation instructions Load Distribution Sub-Rack