Installation Instructions IM584000300 Spec. No. 584000300 (Model 4015-X003) Issue AB, April 3, 2013 Chapter 3. Making Electrical Connections Page 27
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 3-9 IT Rack and Conduit Grounding Connections
Rear
EmersonNetwork Power
DCMIT Rack
GroundBar
(1/4-20Captive Nuts
on5/8Centers)
(RecommendedTorque:
84in-lbs [9 Nm])
To
Site
Ground ToIT Rack
FrameGround
Suggested
Connection
Points
ToSub-Rack(s)
GroundingStud
ToHRMG Ground
(ifrequired)
ToNPG Ground
(ifrequired)
ConduitGrounding Points
(StrippedWire Type Connection)
(WireSize Capacity: see below)
(RecommendedTorque: see below)
14-10AWG (2.5-6mm2) 20in-lbs (2 Nm)
8AWG (10mm2) 25in-lbs (3 Nm)
6-4AWG (16-25mm2) 35in-lbs (4 Nm)
LoadDistribution
Sub-Rack
FrontView