Sub-Racks Electrical Interconnections

If the system components are furnished loose to be installed in a customer furnished IT rack, the following electrical interconnections are required.

Connecting the Load Distribution Sub-Rack(s) to the Power and Control Sub-Rack

Note: If you are connecting “bulk” loads, refer to “Power and Control Sub-Rack Bulk

Output Connections (if required)” on page 40.

Procedure

1)Locate the load distribution sub-rack input cables which are factory connected to the load distribution sub-rack. Route these cables into the power and control sub-rack. Connect these cables to the DC output terminals located inside the power and control sub-rack as follows. Repeat this procedure if a second load distribution sub-rack is furnished. Refer to Figure 3-6.

Connect the cable labeled /+/ to the positive DC output terminals.

Connect the cable labeled /-/ to the negative DC output terminals.

Connecting the Battery Tray(s) to the Power and Control Sub-Rack

Procedure

1)Locate the battery tray output cables which are factory connected to the battery tray. Route these cables into the power and control sub-rack. Cables can be routed from the top or bottom into the power and control sub-rack. Connect these leads to the battery terminals located inside the power and control sub-rack as follows. Repeat this procedure if additional battery trays are furnished. Refer to Figure 3-6.

Connect the cable labeled /+/ to the positive battery terminals.

Connect the cable labeled /-/ to the negative battery terminals.

Connecting the Battery Tray Control and Alarm Harness to Other Battery Trays and/or to the Power and Control Sub-Rack

Procedure

1)If only one battery tray is furnished, locate the control/alarm wire harness exiting the battery tray. Locate the two (2) battery control/alarm connectors located on the rear of the power and control sub-rack. Remove a termination plug from one of these connectors. Connect the extension control/alarm cable between the battery tray control/alarm wire harness and the power and control sub-rack connector which the termination plug was removed from. Refer to Figure 3-7.

2)If more than one battery tray is furnished, use the supplied battery tray control/alarm daisy chain cable as shown in Figure 3-7.

Chapter 3. Making Electrical Connections

Page 21

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy