IM584000300

Installation Instructions

Issue AB, April 3, 2013

Spec. No. 584000300 (Model 4015-X003)

 

 

Power and Control Sub-Rack

Battery Tray Alarm / Control Connections - 2 or More Trays

Internal/External Battery Tray Control/Alarm Connectors

(If an internal or external battery tray is not connected, MUST have termination plugs installed.) (Use either connector.)

Extension Control/Alarm Cable (P/N 554715) (56”)

Rear

Battery Tray

Control/Alarm Daisy Chain Cable (P/N 553614)

Battery Tray

Battery Tray

Rear

Battery Tray

Control/Alarm

Harness

Rear

Battery Tray

Control/Alarm

Harness

1. Remove a termination plug from one of the connectors (either one) located on the rear of the power and control sub-rack.

2. Plug the extension control/alarm cable into the connector the termination plug was removed from.

3. Connect the other end of the extension control/alarm cable into the end of the battery tray control/alarm daisy chain cable.

4. Plug the center connector of the battery tray control/alarm daisy chain cable into the battery tray control/harness of the first battery tray.

5. Plug the remaining end of the battery tray control/alarm daisy chain cable into the battery tray control/harness of the second battery tray.

Figure 3-7(cont’d from previous page)

Internal Battery Tray Interconnections

Page 24

Chapter 3. Making Electrical Connections

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy