IM584000300 Installation Instructions

Issue AB, April 3, 2013 Spec. No. 584000300 (Model 4015-X003)

Page 34 Chapter 3. Making Electrical Connections

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Figure 3-13

External Battery Connections

CUSTOMERCONNECTION
TOEXTERNAL BATTERY STRINGS
BatteryTerminals for 400V DC Battery Strings
(fivesets of 1/4-20 x 1/2studson 5/8centers
fordouble hole lugs, e achpo larity)
Note:These connection po ints are
usedboth for connecting external
batterystrings and the inte rnal
batterytrays. A maximum offive (5)
externaland internal battery strings
(total)can be connected to the power
andcontrol sub-rack. Negative
Battery* Positive
Battery*
++--
(Recommended
Torque:84 in-lbs
[9Nm])

Power and Control

Sub-Rack

RectifierShelf Rear View
(coversremoved)
Control/Alarm
ConnectorPinouts
31
2 4
Battery
Alarm +48Vfor
Battery
Alarm
+48V
Shunt
Trip
RTN
Shunt
Trip
*Note:Battery cables can also be
routedthrough the bottom of the
powerand control sub-rack.
Internal/ExternalBattery Tray
Control/AlarmConnectors
(Useeither connector.)
(Ifan internal or external
batterytray is not connected,
MUSThave termination plugs
installed.)
Termination
Plugs