Emerson 4015 installation instructions Power and Control Sub-Rack

Models: 4015

1 64
Download 64 pages 3.27 Kb
Page 30
Image 30

IM584000300

Installation Instructions

Issue AB, April 3, 2013

Spec. No. 584000300 (Model 4015-X003)

 

 

Power and Control Sub-Rack

HRMG Ground Connection

(HRMG Configurations Only)

(MUST BE PROPERLY

CONNECTED TO GROUND)

Rear View

(covers removed)

A lead exits the rear of the power and control sub-rack in a High Resistance Midpoint Ground (HRMG) configuration. This lead MUST be connected directly to ground for proper operation of the mid-point grounding circuit and the ground fault detection circuit. This lead is 16 AWG, approximately

100” long, and terminated in a ring lug with a 1/4” clearance hole.

Figure 3-5

HRMG Ground Connection (HRMG Configuration Only)

Page 20

Chapter 3. Making Electrical Connections