CHECKING THE SYSTEM SHUTDOWN CIRCUIT

Procedure

1)With the system operating, momentarily depress the System Shutdown pushbutton located on the power and control sub-rack.

2)Verify that the rectifier module AC input circuit breakers located on the power and control sub-rack and the battery circuit breaker located on the internal battery trays open.

3)Restart the system by first turning ON the rectifier module AC input circuit breakers then the battery circuit breaker(s).

CHECKING SYSTEM STATUS

Procedure

1)Observe the status of the indicators located on the ACU+ Controller, rectifier modules, and power and control sub-rack. If the system is operating normally, the status of these is as shown in Table 5-2.

 

Component

 

Indicator

 

Normal State

 

 

 

 

 

 

 

 

 

 

Status

 

 

On

 

 

 

(Green)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACU+

 

Information

 

 

Off

 

 

(Yellow)

 

 

 

Controller

 

 

 

 

 

 

 

 

 

 

 

Warning or

 

 

 

 

 

 

 

 

 

 

 

 

Critical Alarm

 

 

Off

 

 

 

(Red)

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

On

 

 

 

(Green)

 

 

 

 

 

 

 

 

 

Rectifier

 

 

 

 

 

 

 

Protection

 

 

Off

 

Modules

 

(Yellow)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm

 

 

Off

 

 

 

(Red)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage

 

On

 

 

 

Present (Green)

 

 

 

 

 

 

 

 

 

 

 

 

 

Power and

 

PS1 Indicator (Green)

 

On

 

Control

 

PS2 Indicator (Green)

 

On

 

Sub-Rack

 

Ground Fault Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(HRMG Configurations Only)

 

Off

 

 

 

(Red)

 

 

 

 

 

 

 

 

 

 

 

Table 5-2

 

 

 

 

Status and Alarm Indicators

 

Page 50

Chapter 5. Initially Starting the System