IM584000300 | Installation Instructions |
Issue AB, April 3, 2013 | Spec. No. 584000300 (Model |
|
|
VERIFYING THE CONFIGURATION FILE
For factory configured systems, your ACU+ was programmed with a configuration file that sets all adjustable parameters. The version number of the configuration file can be found on the configuration drawing
Procedure
Note: When viewing any of the following screens, if a key is not depressed within approximately 10 seconds, the ACU+ will automatically return to the Main screen.
1)With the Main screen displayed, press ESC. A screen displays the serial number and software version.
2)Press ENT. A screen displays the hardware version and MAC address.
3)Press ENT. A screen displays the configuration version number.
4)Press ESC, or wait approximately 10 seconds, to return to the Main screen.
CHANGING BATTERY CAPACITY RATING IN THE ACU+
To change the battery capacity setting of the ACU+ to match the battery connected to the power system, perform the following procedure.
Procedure
1)With the Main screen displayed, press ENT to go to the Main Menu. Navigate to and select “Settings” (ENT).
2)If a password screen opens, a password must be entered to allow the User to make adjustments. If a password was previously entered and has not yet timed out, skip this step and proceed to step 3). Otherwise, to enter a password, with the cursor at the User Name field (default is “Admin”), press the down arrow key to move cursor down to the password line. Press ENT. “0” is highlighted. Press the up arrow key once to change the “0” to”1” (default password is “1”), then press ENT twice. (Note: If you have been assigned a unique User Name and password, follow this procedure to enter these.)
3)With the Settings menu screen displayed, navigate to and select “Battery” (ENT) / “Basic” (ENT).
4)Navigate to “Rated Capacity”. Press ENT. Use the up or down keys to adjust the value as required. Press ENT.
Note: For NetSure 4000 Series Battery Tray's, the capacity value is 8.5
5)Return to the Main screen by repeatedly pressing ESC (escape).
Page 46 | Chapter 5. Initially Starting the System |
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.