IM584000300 Installation Instructions

Issue AB, April 3, 2013 Spec. No. 584000300 (Model 4015-X003)

Page 30 Chapter 3. Making Electrical Connections

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Figure 3-11

DC Load Distribution Connections to Distribution Sub-Rack(s)

Load Distribution Sub-Rack

(HRMG Configurations)

Load Distribution Sub-Rack

(NPG Configurations)

Load Connections
(See Detail A)
(StrippedWire
TypeConnection)
Load Connections
(See Detail B)
(StrippedWire
TypeConnection)
DETAILA
Load Connections to
Load Distribution Circuit Breakers
Front
(coverremo ved)
+-
WireSize Capacity:
10-4AWG (6-25mm2)
RecomendedTorque:
18in-lbs (2 Nm)

±200V DC

factory
connection
WireSize Capacity:
10-4AWG (6-25mm2)
RecomendedTorque:
80in-lbs [9 Nm])
Return(-)
ReturnBa r
+400VD C
Front
(coverremo ved)
DETAILB
Load Connections to
Load Distribution CircuitBre akersand Return Bar
WireSize Capacity:
10-4AWG (6-25mm2)
RecomendedTorque:
18in-lbs (2 Nm)
Field Connectiont o
ExternalC ustomer Loads.
OBSERVECORRECT POLARITY.
FieldC onnectionto
ExternalC ustomer Loads.
OBSERVECORRECT POLARITY.
CONNECTONLY TO "+"
SIDEOF BREAKER,
ASSHOWN.
Caution: In the NPG Configuration,
thisequipment will have (after installation)
aconnection between the earthed conductor
ofthe DC power supply circuit and the earthing
conductor.