Model NGA 2000 TO2
Instruction Manual
a.Leak Test
The TO2 Analyzer Module is completely tested at the factory for gas leakage. The user is responsible for testing for leakage only at the inlet and outlet fittings on the rear panel.
CAUTION.
SENSOR DAMAGE
Do not expose the Sensor to pressure in excess of 1.0 psig as this may cause dam- age.
Flow Indicator Method
Supply air or inert gas such as nitrogen, at 1 psig (6.8 hPa), to the analyzer through a flow indicator with a range of 0 to 250 cc/min. Install a
Close the outlet
2-6 ELECTRICAL CONNECTIONS
WARNING.
ELECTRICAL SHOCK HAZARD
Operate this equipment only when covers are secured. Servicing re- quires access to live parts which can cause death or serious injury. Refer servicing to qualified personnel. For safety and proper performance, this module must be connected to a properly grounded
Electrical connections must be made in compliance with National Electri- cal Code (ANSI/NFPA 70) and/or any applicable national or electrical codes.
Two electrical connections are required on the Analyzer Module: POWER and NETWORK (See Figure
2)
Connect a source of 24 V 5A DC power to the power inlet. Make sure that the ground con- nection is made, and that this is separate from the power return lead. Failure to ensure a good ground may result in random noise and disturbance in the analyzer readings.
Rosemount Analytical Inc. A Division of Emerson Process Management | Installation |