Selecting Power Supply Cords
Black Diamond SSI DC PSU, Model 60021:
●Wire: three conductor, 8 AWG, jacketed, and marked 90C min
NOTE
Tray Cable is a UL
●Wall plug: N/A,
●Device connector: Molex Shell Connector PN
●Assembly rating: 75VDC, 30A, (Do not disconnect under load)
Black Diamond 325 W AC PSU Model 65021:
●Wire: 18 AWG (0.82mm2) minimum,
●Wall plug: Suitable for use in country of installation & approved by local regulatory authority
●Device connector:
●Power cord assembly: Must be rated at 10A by
Black Diamond 325 W DC PSU, Model 60021:
●Wire: UL LISTED, three conductor, 14 AWG, jacketed, and marked (UL) FT2, 90C min
NOTE
Tray Cable is a UL
●Wall plug: N/A,
●Device connector: Molex Shell Connector PN
●Assembly rating: 75VDC, 30A, (Do not disconnect under load)
WARNING!
When using multiple power supplies, make sure that each power supply is attached to independent circuits breakers. See PS installation instructions of PS for proper sizing of circuit breaker.
Make sure that the source outlet is properly grounded according to the country’s local electrical requirements before plugging the AC supply power cord into a PSU.
For specific product input power requirements refer to the data sheet of the product or modular PSU at http:// www.extremenetworks.com or to Appendix B of this guide.
The following countries have specific safety instructions concerning power connectors:
●Argentina: The supply plug must comply with Argentinean standards.
●Australia: Use AS 3112 for 110/220 VAC power supplies.
●Denmark: The supply plug must comply with section
●International: Use CEE 7/7 for 110/220 VAC power supplies.
●Japan:
BlackDiamond 12800 Series Switches Hardware Installation Guide | 137 |
|
|