Installing the BlackDiamond 12800 Series Chassis

Figure 37: Securing the BlackDiamond 12802 Switch to the Rack (Mid-mount Position)

Screws (x4)

Rack

Screws

BD_152

Grounding the BlackDiamond 12800 Series Chassis

Although grounding the BlackDiamond 12800 series chassis is optional, it is recommended. A grounding point with integrated pem-nuts is provided on the back of the chassis.

You need the following materials to ground the chassis:

Two 10-24 screws, 1 inch or shorter

One copper, standard barrel 2-hole compression grounding lug, type LDC, equivalent to Panduit part number LCD4-14A-L or Thomas & Betts part number: LCN4-14

Appropriate grounding wire for your system, based on the available input current for the power supply:

For AC systems using a 20A breaker per PSU (SSI AC), the chassis ground can be as small as 14 AWG.

For DC systems using a 40A breaker per PSU (SSI DC), the chassis ground can be as small as 10 AWG.

68

BlackDiamond 12800 Series Switches Hardware Installation Guide

 

 

Page 68
Image 68
Extreme Networks 12804, 12802 manual Grounding the BlackDiamond 12800 Series Chassis