vFollow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
vSee the Problem Determination and Service Guide on the IBM System x Documentation CD to determine which components are customer replaceable units (CRU) and which components are field replaceable units (FRU).
vIf an action step is preceded by “(Trained service technician only),” that step must be performed only by a trained service technician.
Error code | Description | Action |
| |
|
|
|
|
|
1804 | No more memory (below 1 MB for a PCI | 1. | Remove the failing adapter | |
| adapter). | |||
| 2. | Reseat each adapter | ||
|
| |||
|
| 3. | Replace the following components one at a time, | |
|
|
| in the order shown, restarting the server each | |
|
|
| time: | |
|
|
| a. | Each adapter |
|
|
| b. (Trained service technician only) | |
|
|
|
|
|
1805 | PCI option ROM checksum error. | 1. | Make sure that the settings for the adapter and all | |
|
| |||
|
|
| other adapters in the Configuration/Setup Utility | |
|
|
| program are correct. | |
|
| 2. | If the error code indicates a particular PCI or | |
|
|
| ||
|
| 3. | Reseat each adapter | |
|
| 4. | Replace the following components one at a time, | |
|
|
| in the order shown, restarting the server each | |
|
|
| time: | |
|
|
| a. | Each adapter |
|
|
| b. (Trained service technician only) | |
|
|
|
|
|
1806 | PCI | 1. | Make sure that the settings for the adapter and all | |
|
| |||
|
|
| other adapters in the Configuration/Setup Utility | |
|
|
| program are correct. | |
|
| 2. | If the error code indicates a particular PCI or | |
|
|
| ||
|
| 3. | Reseat each adapter | |
|
| 4. | Replace the following components one at a time, | |
|
|
| in the order shown, restarting the server each | |
|
|
| time: | |
|
|
| a. | Each adapter |
|
|
| b. (Trained service technician only) | |
|
|
|
|
|
1807, 1808 | General PCI error. | 1. | Make sure that no devices have been disabled in | |
|
| |||
|
|
| the Configuration/Setup Utility program. | |
|
| 2. | Reseat the failing adapter. | |
|
|
| Note: If an error LED is lit for a specific adapter, | |
|
|
| reseat that adapter first; if no LEDs are lit, reseat | |
|
|
| each adapter one at a time, restarting the server | |
|
|
| each time, to isolate the failing adapter. | |
|
| 3. | Replace the following components one at a time, | |
|
|
| in the order shown, restarting the server each | |
|
|
| time: | |
|
|
| a. | Each adapter |
|
|
| b. (Trained service technician only) | |
|
|
|
|
|