Light path diagnostics LEDs

The following table describes the LEDs on the light path diagnostics panel and suggested actions to correct the detected problems.

vFollow the suggested actions in the order in which they are listed in the Action column until the problem is solved.

vSee the Problem Determination and Service Guide on the IBM System x Documentation CD to determine which components are customer replaceable units (CRU) and which components are field replaceable units (FRU).

vIf an action step is preceded by “(Trained service technician only),” that step must be performed only by a trained service technician.

Lit light path

 

 

 

 

diagnostics LED with

 

 

 

 

the system-error or

 

 

 

 

information LED also

 

 

 

 

lit

Description

Action

 

 

 

 

All LEDs are off (the

 

No action is necessary.

power LED is lit; the

 

 

 

 

information LED might

 

 

 

 

be lit).

 

 

 

 

 

 

 

 

 

POWER SUPPLY 1

Power supply 1 has failed or has

1.

Reinstall the power supply 1.

 

been removed.

 

2.

Check the individual power-supply LEDs.

 

Note: In a redundant power

 

3.

Reseat the following components:

 

configuration, the dc power LED on

 

one power supply might be off.

 

a.

Power supply

 

 

 

b. (Trained service technician only) Power

 

 

 

 

backplane

 

 

4.

Replace the components listed in step 3, one at a

 

 

 

time, in the order shown, restarting the server each

 

 

 

time.

 

 

5.

If a 240 V ac fault has occurred, remove ac power

 

 

 

before restoring dc power.

 

 

 

 

 

POWER SUPPLY 2

Power supply 2 has failed or has

1.

Reinstall the power supply 2.

 

been removed.

 

2.

Check the individual power-supply LEDs.

 

Note: In a redundant power

 

3.

Reseat the following components:

 

configuration, the dc power LED on

 

one power supply might be off.

 

a.

Power supply

 

 

 

b. (Trained service technician only) Power

 

 

 

 

backplane

 

 

4.

Replace the components listed in step 3, one at a

 

 

 

time, in the order shown, restarting the server each

 

 

 

time.

 

 

5.

If a 240 V ac fault has occurred, remove ac power

 

 

 

before restoring dc power.

 

 

 

 

 

CONFIG

Microprocessor configuration error.

1.

Mismatched microprocessors, remove and install

 

 

 

 

 

two microprocessor of the same cache size, type,

 

 

 

and clock speed.

 

 

2.

Check the system error log for information

 

 

 

indicating incompatible components.

 

 

 

 

 