Specifications

5.5Electrical Specifications

RECTIFIER INPUT

 

Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC

Input Voltage

Standard voltages for 500 - 1000kVA units: 480 and 600VAC

 

Other voltages available on request. 3-phase, 3-wire plus ground.

Voltage Range

+10%, -15% (no battery discharge at -20%)

Frequency Range

57 Hz to 63 Hz

 

Less than 3 times normal full load input current for UPS models without optional

Subcycle Magnetization Inrush

input isolation transformer. Typically less than 8 times normal full load input current

 

for models with optional input isolation transformer and optional input filter.

Input Current Walk-In

From 20% to 100% in 15-20 seconds

Current Limit

Maximum of 125% normal full load input current

 

Less than 30% reflected THD typical at normal full load input current. Less than 7%

 

reflected THD typical at normal full load input current with optional input filter.

Current Distortion

For models with optional 12-pulse rectifier, less than 9% reflected THD typical at

 

normal full load input current. Less than 4% reflected THD typical with optional input

 

filter.

Power Factor

0.85 minimum lagging at full load

0.92 minimum lagging at full load with optional input filter

 

BYPASS INPUT

 

 

Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. 3-phase, 3-wire

Input Voltage

plus ground or 3-phase, 4-wire plus ground. Other optional voltages available.

Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground

 

 

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Range

±5% for manually initiated bypass transfer

±10% for automatically initiated uninterrupted transfer

 

Frequency Range

59.5 Hz to 60.5 Hz

Voltage Transient

±4% for manually initiated bypass transfer

CRITICAL LOAD OUTPUT

 

 

Standard voltages - 208/120 VAC, 480/277 VAC and 600/347 VAC. 3-phase, 3-wire

Output Voltage

plus ground or 3-phase, 4-wire plus ground. Other optional voltages available.

Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground

 

 

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Regulation

±0.5% for balanced load

±2% for unbalanced load

 

Voltage Adjustment Range

±5% manually (front panel knob)

Line Drop Compensation Range

Up to +5% automatic load dependent

Frequency

59.5 Hz to 60.5 Hz

Slew Rate

0.01 to 1 Hz per second adjustable

Phase Balancing

120° ±1° for balanced loads

120° ±3° for 50% unbalanced loads

 

Voltage Imbalance

 

20% Unbalanced Load

50% Unbalanced Load

±1% from the arithmetic average of the 3 phases ±2% from the arithmetic average of the 3 phases

Voltage Transient

20% Load Step

±4% RMS

50% Load Step

±4% RMS for 100-750kVA units; ±5% RMS for 1000kVA units

100% Load Step

±5% RMS for 100-750kVA units; ±8% RMS for 1000kVA units

Loss or Return of AC Input Power

±1% RMS

Manual Transfer of 100% Load

±4% RMS

Voltage Transient Recovery Time

To within 1% of steady state output voltage within 50 milliseconds

Voltage Harmonic Content

Maximum 5% RMS total, for any combination of linear and nonlinear 3-phase loads

Maximum 3% RMS single, for linear loads

 

 

104% of full load rating continuously

Overload at Full Output Voltage

125% of full load rating for 10 minutes

150% of full load rating for 30 seconds

 

 

(with ±2% voltage regulation)

 

Up to 300% of normal full load current subcycle; up to 500% of normal full load

Fault Clearing

current for up to 40 milliseconds with bypass available; up to 1000% of normal full

 

load current for up to 16 milliseconds with bypass available.

96

Page 102
Image 102
Liebert 610 manual Electrical Specifications