3.3.5Off Battery

The battery plant can be disconnected from the UPS, if required for battery maintenance, by opening the module battery disconnect (MBD) circuit breaker. In this situation the UPS module will continue to supply conditioned power to the critical load, but if input power fails the UPS system cannot sup- ply power to the load.

! CAUTION

When the UPS system is operating with the module battery disconnect (MBD) circuit breaker(s) open, the critical load is not protected from loss of the utility source power.

Figure 46 Load on UPS—battery not available

THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD

BFB

MBB

 

Critical

 

Load

 

AC Output

BIB

MIB

UPS MODULE

Static

Switch

Disconnects

Static

Bypass

Switch

Bypass CB

CONTROL POWER

RIB

INPUT

CB

MAIN INPUT

SWITCHGEAR

Controls

Rectifier/

Charger

Inverter

OUTPUT

CB

Battery

MBD

63