Liebert 610 manual Monitor/Mimic Display Screen, Input Metering Displays, Output Metering Displays

Models: 610

1 104
Download 104 pages 35.06 Kb
Page 29
Image 29

Operation

3.2.2Monitor/Mimic Display Screen

From Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the Select pad and the Monitor/Mimic screen is displayed.

Figure 7 Monitor/Mimic display screen

 

 

1

© 1989-2003

BYPASS INPUT

A-B B-C C-A

 

 

 

480V

480V

480V

 

 

 

 

60.0 Hz

2

 

 

4

 

 

 

 

 

 

UPS RATINGS

UPS INPUT PWR

AP658-64

 

RATED 500 KVA

A-B

B-C

C-A

OUTPUT VOLTAGE

480V

480V

480V

A-B

B-C

C-A

350A

350A 350A

 

 

3

480V

480V

480V

 

 

 

 

60.0 Hz

6

BATTERY

 

 

5

 

 

 

LOAD

 

270 KVA / 217 KW

A

B

C

325A

325A

325A

7

 

 

VOLTS 540 AMPS 15 CHARG

OK to Transfer

Static Switch Connected

The Monitor/Mimic display screen is a simplified block diagram of the UPS system. This screen gives the operator an overall view of the power flow through the UPS system. The screen consists of three major sections: the input/UPS metering section, the load metering section and the status and alarm message areas. The metered parameter values on the Monitor/Mimic screen are updated at one-sec- ond intervals.

NOTE

All voltage readings are phase-to-phase measurements (A-B, B-C and C-A). All current readings are phase measurements (A, B and C).

Input Metering Displays

Item 1 - Bypass Input: This block displays the bypass input voltage and the bypass input frequency. The bypass circuit breaker is shown to the right of this block. The status of the circuit breaker is illus- trated as open or closed.

Item 2 - UPS Input Pwr: This block displays the UPS input voltage and current. The input circuit breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Item 3 - Battery Block: This block displays the DC bus voltage and the charge or discharge current to or from the battery. This block reads MODULE DC BUS when the battery circuit breaker is open and BATTERY when the battery circuit breaker is closed during normal operation. This block reads BATTERY EQUALIZE when the battery equalize charge voltage is used to recharge the battery. This block also shows BATTERY TEMPERATURE when the battery temperature sensor option is installed. The Module Battery Disconnect (MBD) is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Output Metering Displays

Item 4 - UPS Ratings: This block displays the UPS module part number and kVA rating. The UPS output voltage and frequency are also displayed in this block. The output circuit breaker is shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.

Item 5 - Load: This block displays the total output power to the critical load in kVA and kW. The critical load current per phase is also displayed in this block. Note that kW is not displayed when the load is on the bypass line. During an overload condition, the time remaining before transfer is dis- played at the bottom of the load box.

23

Page 29
Image 29
Liebert 610 manual Monitor/Mimic Display Screen, Input Metering Displays, Output Metering Displays