Operation

The Summary screen (Figure 18) shows Total Number of Discharge Cycles, Accumulated Battery Time, Accumulated Battery Amp Hours, Accumulated Battery Kilowatt Hours and Battery Tempera- ture. During a battery discharge event, the screen changes to show information about the present dis- charge cycle. The screen displays Active Cycle Time in place of Accumulated Battery Time and shows Active Battery AH and Active Battery kWH instead of accumulated values.

Figure 18 Battery cycle monitoring summary screen

©1989-2003SELECT : EXIT

Battery Cycle Monitoring Summary

Total No. of Cycles

7

Accumulated Battery Time

15 min. 32 sec.

Accumulated Battery AH

71

Accumulated Battery KWH

34

Battery Temperature

25°C / 77°F

Figure 19 shows a typical detail screen for the 91-240 Seconds Discharge category. This information can be collected remotely, through the optional communications board and modem, by a remote termi- nal or a personal computer equipped with a modem and communications program. See 3.2.14 - Com- munication Interfaces for more information.

Some screens, like the Battery Cycle Monitor information, contain data that you may wish to import into a spreadsheet for further calculations. To put this data into a usable format, use the screen-cap- ture feature of your communications software (or a separate screen-capture program) to save all or part of the data to disk.

NOTE

If you save the file with an extension of “.txt,” it can be imported into a spreadsheet program and converted to worksheet format.

Figure 19 Typical data on discharge cycles of 91 to 240 seconds duration during the recording period

 

 

 

 

 

 

 

 

UP

: CURSOR UP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN : CURSOR DOWN

 

 

 

 

 

 

 

 

 

 

Total

91-240 se c. Cycl

5

© 1989-2003

SELECT : CHOOSE

 

EXIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Event

Date

Time

Duration

Min. Volt

Max. Amp

Start KW Start Temp

15

4/12/95

10:31

235

477

110

 

70

68

12

3/25/95

20:21

98

479

97

 

37

65

9

3/13/95

7:35

139

467

173

 

69

67

5

2/07/95

17:22

199

478

95

 

40

70

2

11/24/94

12:33

95

477

83

 

39

69

31