Operation

Remote Monitor Panel

The Liebert Remote Monitor Panel provides an LED indication of the following conditions:

Load On UPS

Load On Bypass

Battery Discharge

Low Battery Warning

Overload

Ambient Overtemp

System Summary Alarm

New Alarm

This information is also available for customer use through a set of contacts on a separate terminal board.

Alarm messages that activate the System Summary Alarm are listed in Table 1 and Table 2.

The Remote Monitor Panel housing is a NEMA Type 1 enclosure, available for either surface-mount or flush-mount installations.

Separate / Simultaneous Outputs

The RS-232 interface can support a modem plus either a local terminal or a local monitor. The SiteScan port can support either SiteScan or SNMP communications. Whatever communication options are installed in the Series 610 UPS can all be used simultaneously.

Table 6

Series 610 terminal commands

 

 

 

 

Key(s)

Function

 

 

 

A, return

 

Displays Present Status Report screen.

 

 

 

^B (control-B), return

Displays Event History Report screen, starting with the most recent frame and then

scrolling back through earlier frames.

 

 

C, return

 

Displays History Status Report screen starting with the most recent frame and then

 

scrolling back through the earlier frames.

 

 

F (no return)

Freezes data output. This stops the data scrolling on the monitor to allow closer study or a

printout. This is a toggle switch command. Press the “F” key again to resume data scrolling.

 

 

 

 

Resets (unfreezes and clears) the History Status Report memory buffer. This erases the

G, return

 

alarm messages and meter indications that were stored immediately before and after a

 

significant system fault. NOTE: Do not reset the History Status Report memory buffer until

 

 

 

 

operation and maintenance personnel have reviewed it as a troubleshooting tool.

 

 

 

 

 

The data output stops (quits). The UPS communication system remains on stand-by, ready

Q (no return)

to receive the next communication command. NOTE: To return to the beginning of the

 

 

Event History or History Status Report, press Q, then request your desired report again.

d mm/dd/yy, return

This entry sets the date (month/day/year) in the UPS system clock. You must include the

slash (/) as you key in the date. Note that the d command must be lower case.

 

 

t hh:mm:ss, return

This entry sets the time (hour:minute:second) in the UPS system clock. You must include

the colon (:) as you key in the time. Note that the t command must be lower case.

 

 

H, return

 

Prompts the UPS system to hang up its modem (only applicable to the modem

 

communications port).

 

 

I, return

 

Display Battery Cycle Monitor information for 0-30 second discharge events.

 

 

 

J, return

 

Display Battery Cycle Monitor information for 31-90 second discharge events.

 

 

 

K, return

 

Display Battery Cycle Monitor information for 91-240 second discharge events.

 

 

 

L, return

 

Display Battery Cycle Monitor information for over 240 second discharge events.

 

 

 

M, return

 

Display Status Summary screen of battery discharge events.

 

 

 

N, return

 

Show detail information on all battery discharge events in order of occurrence (last in, first

 

out).

 

 

backspace

 

Moves cursor left to cancel previous entry or command.

 

 

 