Liebert 610 manual Present Status, Event History

Models: 610

1 104
Download 104 pages 35.06 Kb
Page 34
Image 34

Operation

Present Status

The Present Status screen shows the current status of the UPS module. This screen displays any alarm messages that are present and the values of the metered parameters for each cabinet.

Each update sequence (every 4 milliseconds) is called a frame. The frame number is displayed in the upper right corner. The Present Status screen display is updated every two seconds.

Battery Time Remaining (in minutes) is displayed on the module screens during a battery discharge. The value is on the Battery Volts line in the TIME column (far right side of the screen). For the first two minutes of discharge, the Rated Time Remaining is displayed. After that, the Calculated Time Remaining is displayed and updated every six seconds.

All the information on this screen, including Battery Time Remaining, is available to a local terminal or modem through the communications ports provided in the Series 610 UPS. Refer to Table 6 in this manual for keyboard commands to use with the communication ports.

Figure 14 Present status report screens

PRESENT STATUS

MODULE-0

01/12/96

14:06:26 FRAME 35

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging

 

 

 

A

B

C

DC

LOAD HERTZ TIME

OUTPUT VOLTS

480

480

480

 

 

OUTPUT AMPS

325

325

325

 

60.0

OUTPUT FREQUENCY

 

 

480

BATTERY VOLTS

 

 

 

0:09

BATTERY AMPS

 

 

 

-645

 

INPUT VOLTS

0

0

0

 

 

INPUT AMPS

0

0

0

 

 

LOAD KVA

 

 

 

 

270

END OF REPORT

SELECT : EXIT

Event History

The Event History screen lists the active alarms present in the UPS. This screen also displays the prior 128 alarm frames, in a first in, first out (FIFO) sequence, that have taken place along with the date and the time that each alarm frame occurred. Use the Up and Down pads to look through the different alarm frames.

Figure 15 Event history report screen

EVENT HISTORY

MODULE-0

01/17/96 11:23:41 FRAME 175

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging

Low Batt Warning

UP : NEXT FRAME

DOWN : PREVIOUS FRAME

SELECT : EXIT

28

Page 34
Image 34
Liebert 610 manual Present Status, Event History