Operation

3.3.7Remote Emergency Power Off

The Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load.

The Remote Emergency Power Off control is a user-provided switch located remotely from the UPS system. It will normally be in the same room as the critical load equipment. This mode can also be ini- tiated by an automatic contact closure in the same external circuit as the manually operated switch.

When you operate the Remote Emergency Power Off switch, all UPS circuit breakers are opened, including the bypass circuit breaker. All power through the UPS is removed from the load. Typically, the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS controls.

Refer to 3.4.4 - Shutdown Procedures.

Figure 48 Emergency power off

THREE BREAKER MAINTENANCE BYPASS SWITCHBOARD

BFB

MBB

 

Critical

 

Load

 

AC Output

BIB

MIB

RIB

UPS MODULE

Static

Bypass

Switch

Static

 

Switch

Bypass CB

Disconnects

CONTROL POWER

Controls

MAIN INPUT

SWITCHGEAR

INPUT

CB

Rectifier/

Charger

Inverter

OUTPUT

CB

Battery

MBD

65

Page 71
Image 71
Liebert 610 manual Remote Emergency Power Off, Emergency power off