Operation
Figure 9 Monitor/Mimic display example: Utility fail
BYPASS INPUT
UPS INPUT PWR | ||
0V | 0V | 0V |
0A | 0A | 0A |
BATTERY
VOLTS 480
AMPS 645 DISCHARG
©
UPS RATINGS | ||
|
| |
RATED 500 KVA | ||
OUTPUT VOLTAGE | ||
480V | 480V | 480V |
| 60.0 Hz |
|
Not OK to Transfer Static Switch Connected
| LOAD |
|
270 KVA / 217 KW | ||
A | B | C |
325A | 325A | 325A |
Byp Not Avail
Input Fail
Batt Discharging
Figure 10 Monitor/Mimic display example: Load on bypass, UPS module on and charging battery
BYPASS INPUT | ||
479V | 480V | 480V |
| 60.0 Hz |
|
UPS INPUT PWR | ||
480V | 480V | 480V |
390A 390A | 390A |
BATTERY
VOLTS | 540 |
AMPS | 75 CHARG |
©
UPS RATINGS | ||
|
| |
RATED 500 KVA | ||
OUTPUT VOLTAGE | ||
480V | 480V | 480V |
| 60.0 Hz |
|
OK to Transfer
Static Switch Connected
| LOAD |
|
270 KVA / 217 KW | ||
A | B | C |
325A | 325A | 325A |
Load On Bypass
Figure 11 Monitor/Mimic display example: Load on bypass, UPS module off
BYPASS INPUT
UPS INPUT PWR | ||
480V | 480V | 480V |
0A | 0A | 0A |
MODULE DC BUS
VOLTS | 0 |
AMPS | 0 CHARG |
©
UPS RATINGS | ||
| ||
RATED 500 KVA | ||
OUTPUT VOLTAGE | ||
0V | 0V | 0V |
| 60.0 Hz |
|
Not OK to Transfer Static Switch Connected
| LOAD |
|
| 270 KVA |
|
A | B | C |
325A | 325A | 325A |
Batt CB Open
Load On Bypass
Input Fail
25