Operation

3.2.6Alarm Limit Settings Screen

Go to the Master Menu and move the highlighted cursor to LIMIT SETTINGS. Press the Select pad and the Limit Settings screen is displayed.

The Alarm Limit Settings screen has Security Access to enable an authorized Liebert field-service engineer to adjust the UPS system alarm limit settings

! CAUTION

All alarm limit settings are application matched and factory-set. They should not be changed casually. Contact Liebert Global Services for changing the alarm limit settings.

Figure 29 Alarm limit settings screen

 

 

 

 

 

 

 

UP : CURSOR UP

SECURITY ACCESS

 

 

 

 

 

 

 

 

 

 

 

© 1989-2003

 

 

DOWN : CURSOR DOWN

 

 

 

 

 

SELECT : CHOOSE

 

 

 

ALARM SETTINGS

 

 

 

 

EXIT

 

 

 

 

 

Overload Alarm

104

%

 

DC Over Voltage

600

VDC

 

Battery Discharging

480

VDC

 

Low Battery

437

VDC

 

Battery Shutdown (15 minutes)

384

VDC

 

 

Upper Point (60 minutes)

427

VDC

 

Battery Rating (100%)

500

KW

15 min

Battery Rating

250

KW

45 min

Temperature Limit Setting

28 C

 

 

 

Overload Alarm

This alarm setting initiates an alarm message on the display screen warning the operator that the UPS system output current has exceeded the specified limit. This condition only activates an alarm. The UPS does not shut down, but a separate control circuit will transfer the critical load to bypass if the current and time of the overload condition exceeds system capability.

DC Overvoltage

This setting limits the maximum permitted level of the DC bus voltage. When this setting is exceeded, an alarm indication appears on the module display screen, the UPS transfers the load to the bypass line, and the input and battery circuit breakers trip open.

NOTE

The following battery alarm settings are factory-adjusted to the battery being utilized.

Battery Discharging

When the battery voltage on the DC bus falls below this limit for 5 seconds, a Battery Discharging alarm message is displayed on the module screen. This means that the battery is discharging due to an input voltage sag or interruption or a module output overload.

Low Battery

While the battery is discharging, this alarm warns the operator that the Battery Shutdown level is approaching. This is generally set for a reserve time of approximately 5 minutes (typically 10 volts above the 60-Minute Battery Shutdown voltage), based on full load operation.

Battery Shutdown (15 Minutes)

When the battery voltage decreases to this limit for five seconds during the first 15 minutes of the dis- charge, the battery circuit breaker opens to prevent overdischarge. Note that the rated battery reserve time at your site may be other than 15 minutes.

40

Page 46
Image 46
Liebert 610 manual Alarm Limit Settings Screen, Overload Alarm, DC Overvoltage, Battery Discharging, Low Battery