Operation
Battery Shutdown (60 Minutes)
During extended outages or deep sags of more than 15 minutes, the shutdown voltage limit will ramp up gradually to this
Battery Rating (100%)
This setting is the full load discharge rating of the battery in kilowatts for the rated backup period. A typical rating might be 500 kW for 15 minutes.
Battery Rating
This setting is a battery discharge rating in kilowatts under partial load for an extended period, typi- cally 40 to 60 minutes. The UPS uses the two battery shutdown voltage settings and the two battery discharge ratings in computing rated and calculated time remaining during a discharge event.
Temperature Limit Setting (Optional)
This setting is visible when the optional
NOTE
The Low Battery alarm setting is designed to be useful at full load battery discharge rates. It is typically set for 10 volts above the
41