5.0SPECIFICATIONS
5.1Rating
The kVA and kW ratings and the nominal voltages and currents for continuous operation are listed on the unit nameplates (inside Operator Control Panel door) and on the System
Connected load kW and kVA are both displayed on the LCD screen when the UPS is powering the load. The approximate connected load power factor may be easily calculated by kW ÷ kVA = pf.
For load power factors between 0.7 lagging and the rated power factor (usually 0.8 or 0.9), the full kVA rating of the unit is available. However, above the rated pf the kW rating will become the limit- ing factor. Note that some models are specifically rated for a 0.9 lagging output power factor.
For loads with power factors below 0.7 lagging or with leading power factors, the UPS output is kVA limited and the UPS System may not meet all of its output performance specifications. Contact Lie- bert Global Services at
Figure 59 Output power envelope for 0.8 and 0.9 pf rated units
| kW |
|
| 1.0 |
|
| 0.9 |
|
| 0.9 x kVA |
|
LEADING | 0.8 | LAGGING |
power factor (pf) | 0.8 x kVA | power factor (pf) |
| 0.7 x kVA | 0.7 |
|
|
Contact Liebert for | Contact Liebert for |
load operation in this | load operation in this |
area | area |
Rated kVA