Liebert 610 manual Maximum Auto-Retransfer Attempts, Maximum auto-retransfer attempts screen

Models: 610

1 104
Download 104 pages 35.06 Kb
Page 39
Image 39

Operation

Maximum Auto-Retransfer Attempts

When a UPS output overload condition exceeds a pre-programmed current-versus-time window, the UPS automatically transfers the critical load to the bypass line. After the overload condition has been corrected, the UPS attempts to automatically retransfer the critical load to the UPS output (unless zero attempts is selected). The Maximum Auto-Retransfer Attempts limits the number of times

(0 to 5) that the UPS attempts to retransfer the load back to the UPS within a one hour time period.

If more than the selected number of overloads occurs during one hour, the critical load remains on the bypass line and must be manually retransferred to the UPS system. Note that you should determine the cause of any overload condition.

NOTE

Note that automatic retransfers are initiated only if the critical load was transferred to the bypass line because of a system overload. If an automatic transfer to bypass occurred for any other reason, an automatic retransfer will not be initiated. Refer to 3.5.3 - Automatic Retransfers to UPS.

To change the Maximum Auto-Retransfer Attempts parameter, do the following:

1.From the System Configuration Screen, press the Up or Down pad to highlight Maximum Auto- Retransfer Attempts.

2.Press the Select pad. The screen below will appear.

3.Press the Up pad to increase the value or the Down pad to decrease it.

Figure 21 Maximum auto-retransfer attempts screen

© 1989-2003

MAX AUTO-REXFER ATTEMPTS

LOWER INPUT

0

UP : INCREASE

DOWN : DECREASE

SELECT : EXIT

VALUE

3

UPPER LIMIT

5

33

Page 39
Image 39
Liebert 610 manual Maximum Auto-Retransfer Attempts, Maximum auto-retransfer attempts screen