MERLIN LEGEND Communications System Release 7.0 | Issue 1 |
Pocket Reference | April 1999 |
|
|
Power and Grounding | 36 |
|
|
—A metallic underground water pipe must be supplemented by the metal frame of the building, a
—Other local metal underground systems or local underground structures such as tanks and piping systems.
—Rod and pipe electrodes, a
—Plate electrode, a minimum of 2 square feet (61 square cm) of metallic surface exposed to the exterior soil.
—
—At least 20 feet (6.1 m) of one or more steel reinforcing rods, each being at least
—20 feet (6.1 m) of bare copper conductor not smaller than #4 AWG, encased in 2 inches (5 cm) of concrete. This electrode must be located within and near the bottom of a concrete foundation or roofing that is in direct contact with the earth.
—Ground ring, consisting of at least 20 feet (6.1 m) of bare copper conductor not smaller than #2 AWG, encircling the building. The ground ring must be in direct contact with the earth and buried at least 2.5 feet (77 cm) below the earth’s surface.
!WARNING:
Do not use a metal underground gas piping system. This is a safety risk.
For most power surges, the following standard grounding requirements provide adequate lightning and surge protection:
—Properly wired/grounded/bonded outside line protectors
—Properly wired/grounded AC outlet
—Properly grounded
—Properly wired connection between
Additional Power Surge Protection
The 391C1, 391A3, 391A2, and 391A1 power supplies have
Occasionally, additional protection may be needed if the customer is located in a heavy lightning area. The following products are available:
—The 147A protector provides AC surge protection for