Chapter4 ConnectingSignals
©NationalInstruments Corporation 4-53 ATE Series User Manual
Mode 1 Output TimingFigure 4-39 details the timing specifications for an output transfer in
Mode1.
Figure4-39. Mode1 Output Timing
Name Description Minimum Maximum
T1 WR*=0toINTR=0 —250
T2 WR*=1toOutput —200
T3 WR*=1toOBF*=0 —150
T4 ACK* = 0 to OBF* =1 —150
T5 ACK* Pulse Width 100 —
T6 ACK* = 1 to INTR = 1 —150
Alltiming values are in nanoseconds.
WR*
OBF*
INTR
ACK*
DATA
T1
T2
T3
T4
T5
T6