Chapter 2 Installation 59

Replacing covers

After you complete all of the cabling requirements as described in the previous sections, you must replace the plastic back cover on the BIP and the 8010co chassis bezel(s) that were removed earlier in these procedures.

Before you replace the covers and bezels, be sure that all cables are routed properly from under the chassis bays, through the rack, and up to the BIP power terminal block. Check that all tie-wraps are secured, and give special attention to the cables at the power terminal strip; the cable leads must be supported to avoid undue stress on the terminal block.

1Replace the plastic back cover on the BIP (Figure 41).

Figure 41 Replacing the plastic back cover on the BIP

3 2 1 3 2 1

 

3 2 1 3 2 1 A1 A2

B2

PS (+)

PS (+)

A/B Input Feed

PS (-)

PS (-)

 

VDC

Lower Shelf

Upper Shelf

Returns

Lower Shelf

Upper Shelf

Input Feeds

 

1

 

2

 

 

 

1 = Back cover (plastic)

2 = Cover screws (x 4)

10410FA

Installing the Breaker Interface Panel for the Ethernet Routing Switch 8010co Chassis

Page 59
Image 59
Nortel Networks 8010co manual Replacing covers, Replacing the plastic back cover on the BIP