Nortel Networks 8010co manual Connecting the a and B -48 VDC input feeds to the BIP 2

Models: 8010co

1 82
Download 82 pages 55.13 Kb
Page 56
Image 56

56Chapter 2 Installation

5Connect the remaining -48 VDC input feeds and returns as required (Figure 38).

Note: Figure 38 shows the attachment of two “A” feeds and two “B” feeds to the BIP. Note that there is a primary and a secondary A feed, as well as a primary and secondary B feed (see Figure 35 on page 53 for configuration details).

Figure 38 Connecting the A and B -48 VDC input feeds to the BIP (2 of 2)

-48 VDC Feeds

 

 

 

 

 

1

3 2 1 3 2 1

 

3 2 1 3 2 1 A1 A2 B1 B2

PS (+)

PS (+)

A/B Input Feed

PS (-)

PS (-)

– 48 VDC

Lower Shelf

Upper Shelf

Returns

Lower Shelf

Upper Shelf

A/B Input Feeds

1 = -48 VDC input feeds (Primary A, Secondary A, Primary B, Secondary B)

10407FA

312755-G Rev 00

Page 56
Image 56
Nortel Networks 8010co manual Connecting the a and B -48 VDC input feeds to the BIP 2