Chapter 2 Installation 63
Initial power-up
Danger: Due to
To power up the 8010co chassis:
1Set the six circuit breakers on the BIP front panel to the off position (O = Off).
2Set the switches for all power supplies in the upper and lower chassis to the off position (O = Off).
You can access the power supply switches with the bezels installed.
3Turn on the input feed power at the DC power source.
Verifying the LEDs
1Verify the following LEDs on the BIP:
—The (white) POWER Indicator on the BIP front panel is on.
—The (green) shelf alarm cable validation LED is on steady.
The green shelf alarm cable validation LED indicates that the shelf alarm cables are installed properly.
(If there is a problem with the shelf alarm cable installation or jumper settings, the red shelf alarm cable fault LED turns on.)
2Set the six circuit breakers on the BIP front panel to the on position ( = On).
3Set the switches for all power supplies in the upper and lower chassis to the on position ( = On).
Note: When you first install a 8010co chassis that contains two or three power supplies, you must turn on two of the power supply units simultaneously. If you wait longer to turn on the second power supply, one of the power supplies can shut down. To correct this condition, turn off both power supplies, wait at least 30 seconds, and then turn on both power supplies again simultaneously.
Installing the Breaker Interface Panel for the Ethernet Routing Switch 8010co Chassis