Alarm output setup

1.From the Setup menu, select the

<Event ( )> tab.

2.Click <Alarm output setup>.

3.Set the camera’s type of alarm output.

If you change the alarm output type, the alarm out button on the monitoring page and alarm output type displayed on Event Setup page will be changed accordingly.

Type

-Normal open : Considers “Open circuit” status of the sensor or alarm input device as normal, and triggers alarm event if becomes “Closed circuit” status.

-Normal close : Considers “Closed circuit” status of the sensor or alarm input device as normal, and triggers alarm event if becomes “Open circuit” status.

4.Set the alarm output button.

Mode: Sets the alarm output method.

There is difference between operations when clicked alarm output button while disabled.

-Pulse : It is activated during the time period specified by the duration (switching interval) and then becomes inactive automatically.

-Active/Inactive : It maintains as activated until the user clicks the button again to make it inactive.

Duration : Set the alarm duration that maintains activated if the mode is set to pulse, from 1 to 15 seconds.

5.When done, click [Apply ( )].

SETUP SCREEN

English _115

Page 115
Image 115