2. Processes and functions
(B) Heating
REMOTE CONTROL |
| THERMO. ON |
| THERMO. ON |
|
| ||
|
|
| THERMO. OFF |
| THERMO. OFF | |||
SENSOR |
|
|
|
|
|
| ||
(Only for wireless |
|
|
|
|
|
| THERMO. ON | |
remote controller) |
|
|
|
|
|
|
| |
SET. +2 °F |
|
|
|
|
|
|
| |
SETTING TEMP. |
|
|
|
|
|
|
| |
SET. |
|
|
|
|
|
|
| |
BODY SENSOR |
|
|
| THERMO. OFF |
| THERMO. OFF | ||
| THERMO. ON | THERMO. ON |
| THERMO. ON | ||||
|
|
|
| |||||
| +2°F |
|
|
|
|
|
|
|
SET TEMP.+7 °F SHIFT |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
SET TEMP. |
|
|
|
|
|
|
| |
|
|
|
|
|
| MORE THAN | MORE THAN | |
|
|
|
| 5 MINUTES | 3 MINUTES | 5 MINUTES | 3 MINUTES |
|
COMPRESSOR | OFF |
| ON | OFF | ON | OFF | ON | |
1 |
|
|
|
|
|
|
|
|
OUTDOOR FAN | OFF |
| ON | OFF | ON | OFF | ON | |
(H OR M) |
|
| ||||||
|
|
|
|
|
|
|
| |
|
|
| 3 SECONDS |
|
|
|
| |
2 |
| OFF |
| L SET SPEED | LL | SET SPEED | LL | SET SPEED |
INDOOR FAN |
| L LL | ||||||
|
| |||||||
2 |
| OFF | ON | OFF | ON | OFF | ON | OFF |
STANDBY |
| |||||||
|
|
|
|
|
|
|
| |
(88°F) |
|
|
|
|
|
|
| |
INDOOR HEAT |
|
|
|
|
|
|
| |
EXCH. |
|
|
|
|
|
|
|
|
COIL | 81°F |
|
|
|
|
|
|
|
TEMP. | 77°F |
|
|
|
|
|
|
|
E2 |
|
|
|
|
|
|
| |
SOLENOID |
|
|
|
| ON (REVERSING CYCLE) |
|
| |
COIL |
|
|
|
|
| |||
|
|
|
|
|
|
| ||
TEMP. |
|
|
|
|
|
|
|
|
OPERATION |
| OFF |
|
|
| ON |
|
|
BUTTON |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
1. | Refer | to | Outdoor Fan Speed Control |
| |
2. | Refer | to | Cold Draft Prevention (Heating) | 1134_THS_I |
Fig. 2
Chart Summary and Explanations
Once the compressor starts, it keeps running for 5 minutes.
Once the compressor stops, it will not start running again for 3 minutes.
If you change the operation mode (HEAT, COOL or FAN) during the heating cycle, the control circuit stops the compressor for 3 minutes.
For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off, the compressor is not controlled by the room sensor.
When set on remote control sensor
Thermo ON: When room temperature is
Compressor ON
Thermo OFF: When the room temperature is 2˚F above the set temperature T˚, (T˚+2 ˚F)
Compressor OFF
When set on body sensor
NOTE: In case of Body sensor, operating temperature is shifted to setting temperature +7˚F.
SM831148