4. Service procedures

 

 

 

Wired

 

 

 

remote

 

 

 

control

 

Possible cause of malfunction

display

 

 

Ceiling panel connection failure

 

P09

 

 

 

 

Activation of

Indoor protection

Fan protective thermostat

P01

protective

 

 

 

 

Float switch

P10

device

 

 

Discharge temperature trouble

P03

 

 

 

 

 

 

 

Outdoor protection

High pressure switch or compressor motor thermal protector is activated.

P04

 

 

 

 

 

 

Open phase detected, AC power trouble

P05

 

 

 

 

 

 

No gas

P15

 

 

 

 

 

 

4-way valve locked

P19

 

 

 

 

 

 

High cooling load

P20

 

 

 

 

 

 

Outdoor fan trouble

P22

 

 

 

 

 

 

Inverter compressor trouble (HIC PCB)

P26

 

 

 

 

 

 

Inverter compressor trouble (MDC)

P29

 

 

 

 

 

 

Simultaneous-operation multi control trouble

P31

 

 

Compressor current failure (overload)

H01

Thermistor

Thermistor open circuit

Indoor heat exchanger temperature sensor (E1)

F01

fault

• Short circuit (indoor)

 

 

Indoor heat exchanger temperature sensor (E2)

F02

 

 

 

 

 

 

 

 

Indoor temperature sensor

F10

 

Thermistor open circuit

Discharge temperature (TD)

F04

 

• Short circuit (outdoor)

 

 

 

Outdoor heat exchanger temperature (C1)

F06

 

 

 

 

 

 

 

 

Outdoor heat exchanger temperature (C2)

F07

 

 

 

 

 

 

Outdoor air temperature (TO)

F08

 

 

 

 

 

 

Intake temperature (TS)

F12

 

 

Indoor EEPROM error

F29

 

 

Outdoor EEPROM error

F31

Wireless

remote controller receiver display

Operation

Timer

Standby

Alternately

Alternately

Alter.

Alter.

Simul.

Simul.

4

SM831148

IV-3

Page 149
Image 149
Sanyo TH4272R / CH4272R, XH4272R / C4272R, UH2672R, XH2672R, UH3672R / CH3672R, XH3672R, XH4272R / CH4272R Service procedures