4. Service procedures

(2) LED Indicator Messages on Outdoor Control PCB

 

 

 

LED 1

 

LED 2

Remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power ON sequence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. No communication from indoor units in system

 

 

 

 

 

 

 

 

 

 

 

 

 

If it is not possible to

2. Communication received from 1 or more indoor units in system

 

 

 

 

 

 

 

 

 

 

 

 

 

advance to 3, repeats 1 2.

 

 

 

 

 

 

 

 

 

 

 

 

 

At 3, changes to normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Regular communication OK (Capacity and unit quantity match)

 

 

 

 

 

 

 

 

 

 

 

 

 

control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Displayed during automatic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM error (F31)

 

 

 

 

 

 

 

 

 

 

 

 

 

address setting 1 and initial

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communication. After these are

 

 

 

 

 

 

 

 

 

 

 

 

 

 

completed, alarm F31 is displayed.

Pre-trip (insufficient gas)

 

 

 

 

 

 

 

 

P03

 

 

(0.25/0.75)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pre-trip (P20)

 

 

 

 

 

 

 

 

 

 

 

(0.75/0.25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pre-trip (other)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm

Alternate blinking during alarms

LED 1 blinks M times, then LED 2 blinks N times.

 

 

The cycle then repeats.

 

 

 

M = 2: P alarm

3: H alarm

4: E alarm 5: F alarm 6: L alarm

 

 

N = Alarm No.

 

 

 

 

 

 

 

 

* Refer to 1. Examples of alarm displaybelow.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Insufficient gas indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant recovery mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address setting in progress

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking alternately

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address setting alarm (E15)

 

 

 

 

(0.25/0.75)

Blinking simultaneously

 

 

(0.25/0.75)

 

 

 

 

 

 

 

 

Automatic address setting alarm (E20)

 

 

 

(0.75/0.25)

 

 

 

(0.75/0.25)

Blinking simultaneously

 

 

 

 

 

 

 

 

 

 

 

Automatic address setting alarm (Other than E15 and E20)

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking simultaneously

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: ON

: Blinking (0.25/0.75) indicates that the lamp illuminates for 0.25 seconds, and then is OFF for 0.75 seconds. Unless otherwise indicated, the blinking is (0.5/0.5).

: OFF

(3) Examples of alarm display (other than E15, E16, and E20)

Alarm / Display

LED 1

Alternately

LED 2

 

 

 

 

P03

( Blinks

2 times )

(Blinks 3 times)

P04

 

( " )

(Blinks 4 times)

P05

 

( " )

(Blinks 5 times)

P31

 

( " )

(Blinks 31 times)

H01

(Blinks

3 times)

(Blinks 1 times)

 

 

 

E04

(Blinks

4 times)

(Blinks 4 times)

 

 

 

F07

(Blinks

5 times)

(Blinks 7 times)

 

 

 

L13

(Blinks

6 times)

(Blinks 13 times)

 

 

 

Note:

This table shows example alarms. Other alarms may also be displayed.