4. Service procedures

Sensor Temperature Display Function (Displayed both when operating and stopped)

The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures.

<Check procedure>

(1)Press and hold the button and button simultaneously for 4 seconds or longer.

(2)Unit No. X-X (main unit No.), item code XX (sensor address), and service monitor 00XX (sensor tem- perature) appear on the remote controller LCD. (See figure.)

(3)Press the temperature setting and buttons and change the item code to the sensor address of the sensor that you want to monitor.

(For the relationship between the sensor address and the sensor type, refer to the below Sensor Tempera- ture Correlation Table.)

(4)During group control and simultaneous operation multi control, press the button and change to the unit that you want to monitor.

(5)Press the button to return to normal remote controller operation.

NOTE

The temperature display reads “- - - - ” for units that are not connected.

If monitor mode is selected during normal operation, the only parts of the LCD that change are those shown in the figure.

All other displays do not change, and remain as they were during normal operation.

Figure: Sample display when discharge temperature at unit No. 1-1 is 185˚F

Sensor Temperature Correlation Table

Sensor installation

Sensor

Sensor type

Sensor

Sensor type

location

address

address

 

 

 

 

 

 

 

 

00

Room temp.

05

 

 

(temp. used for control)*

 

 

 

01

Remote controller temp.

06

Discharge temp.

Indoor unit

02

Indoor intake temp.

07

 

03

Indoor heat exchanger temp. (E1)

08

 

04

Indoor heat exchanger temp. (E2)

09

 

 

 

 

 

 

0A

Discharge temp. (TD)

12

 

0b

13

 

0C

14

Current

 

 

 

 

(AC current)

Outdoor unit

0d

Intake temp. (TS)

15

Outdoor electronic control

 

 

 

 

valve position

 

0E

Outdoor heat exchanger temp. (C1)

16

 

0F

Outdoor heat exchanger temp. (C2)

17

 

10

18

 

11

Outdoor air temp.

19

 

 

 

 

 

* Main unit only when group control is enabled

SM831148

IV-13

4