Sanyo THH3672R / CH3672R, XH4272R / C4272R, UH2672R, XH2672R, UH3672R / CH3672R Defrost control

Models: KH3072R / C3072R C4272R UH2672R / CH2672R UH2672R KH3672R / CH3672R TH2672R / CH2672R XH2672R / CH2672R UH3672R XH2672R / C2672R UH2672R / C2672R KHH2672R / CH2672R CH4272R TH3672R / CH3672R TH2672R / C2672R XH4272R / C4272R TH2672R THH2672R / CH2672R XH3672R / C3672R UH3672R / CH3672R XH2672R KH3672R / C3672R KH2672R / C2672R TH3672R / C3672R TH4272R / C4272R XH4272R / CH4272R KH2672R / CH2672R TH3672R TH4272R / CH4272R KH3072R / CH3072R THH3672R / CH3672R UH3672R / C3672R XH3672R / CH3672R XH3672R

1 180
Download 180 pages 17.39 Kb
Page 114
Image 114

2. Processes and functions

Defrost control

Defrost control

Defrost sequence

Heating operation

(25-minute mask)

1 Frost detection

Defrost start

(reverse cycle defrost)

Defrost in progress

2 Defrost cancel

3 Start-up operation

Operating frequency: 61.8 Hz

Outdoor unit fan: OFF

Electronic control valve: step 300

4-way valve: OFF

Indoor unit fan: OFF

Frost detection

1. Outdoor heat exchanger temperature (C1) method (15-minute mask after operation start)

2

2.Outdoor air temperature is 7°F or above and outdoor heat exchanger temperature (C1) of 0°F or below is detected continuously for 20 seconds.

3.Outdoor air temperature is below 7°F and outdoor heat exchanger temperature (C1) of below (outdoor air temperature -10)°F is detected continuously for 20 seconds.

(2)Defrost cancel

Defrost end conditions

1.Outdoor heat exchanger temperature (C1) rises to 54°F or higher.

2.Outdoor heat exchanger temperature is 45°F or higher continuously for 1 minute.

3.Defrost time of 10 minutes has elapsed.

(3) Startup operation

After defrost ends, the compressors and outdoor unit fan stop for approximately 40 seconds, then operation begins in heating mode.

SM831148

II-8

Page 114
Image 114