2. Processes and functions
Defrost control
Defrost control
Defrost sequence |
Heating operation |
1 Frost detection |
Defrost start |
(reverse cycle defrost) |
Defrost in progress |
2 Defrost cancel |
3 |
•Operating frequency: 61.8 Hz
•Outdoor unit fan: OFF
•Electronic control valve: step 300
•
•Indoor unit fan: OFF
Frost detection
1. Outdoor heat exchanger temperature (C1) method
2
2.Outdoor air temperature is 7°F or above and outdoor heat exchanger temperature (C1) of 0°F or below is detected continuously for 20 seconds.
3.Outdoor air temperature is below 7°F and outdoor heat exchanger temperature (C1) of below (outdoor air temperature
(2)Defrost cancel
•Defrost end conditions
1.Outdoor heat exchanger temperature (C1) rises to 54°F or higher.
2.Outdoor heat exchanger temperature is 45°F or higher continuously for 1 minute.
3.Defrost time of 10 minutes has elapsed.
(3) Startup operation
After defrost ends, the compressors and outdoor unit fan stop for approximately 40 seconds, then operation begins in heating mode.