2. Processes and functions

Terminal plug (CN015)

3P plug (black): Terminal plug for the communications line

At the time of shipment from the factory, the short-circuiting socket (2P, black) is installed between pins 1 and 2 on the terminal plug (terminal = yes).

When central control is used for multiple systems, leave the short-circuiting socket in place only on the outdoor unit with a system address of 1. At all other outdoor units (other than unit No. 1), move the short-circuiting socket to between 2 and 3 (terminal = no). If multiple short-circuiting sockets remain in place during central control, a com- munications failure will occur.

In the case of a single system only (system address = 0), do not remove the short- circuiting socket. (Alarm "E04" will occur.)

Quiet mode

2P plug (white): Enables operation in quiet mode.

 

 

(CN028)

The outdoor unit fan and compressor frequencies are subject to limits during operation.

 

Low-noise operation is enabled when the relay is turned ON.

 

 

 

 

 

 

 

 

 

 

Example of wiring

 

 

 

 

 

 

Relay (field supply) Power

 

 

 

 

1

1

External contact

 

 

 

Quiet mode

 

 

 

 

 

(timer input, etc.: field supply)

 

 

 

2

2

 

 

 

CN028

 

 

 

 

 

 

 

 

 

Outdoor unit control PCB

Note 1: The maximum length of the wiring between the outdoor unit PCB and the relay is

2m.

Lead wire with 2P plug (special-order part: WIRE K/ 623-161-2098)

Relay, field supply, contact input specifications: DC 5 V, 0.5 mA (Recommended relay: Fuji Electric HH62SW, compatible with micro contacts)

Use a commercially available timer (such as the Omron H5 daily time switch).

Table 1. Method of System Address Setting

[S002 (rotary, black), S003 (2P DIP switch, green or blue)]

 

Outdoor system

S002 setting

S003 setting

 

 

 

 

 

address No.

(system address switch)

1P (10s-digit place)

2P (20s-digit place)

 

 

 

 

 

 

 

 

 

 

 

 

 

1 system only

1

0

OFF

OFF

 

 

 

 

 

1

1

OFF

OFF

 

 

 

 

 

2

2

OFF

OFF

 

 

 

 

 

3

3

OFF

OFF

Out-

Out-

Out-

Out-

 

4

4

OFF

OFF

door

door

door

door

 

5

5

OFF

OFF

System

 

 

 

 

6

6

OFF

OFF

 

 

 

 

controller

 

 

 

 

7

7

OFF

OFF

 

 

 

 

 

 

 

 

 

8

8

OFF

OFF

 

 

 

 

 

9

9

OFF

OFF

 

 

 

 

 

10

0

ON

OFF

In-

In-

In-

In-

 

11

1

ON

OFF

 

door

door

door

door

Central

12

2

ON

OFF

 

 

 

 

13

3

ON

OFF

 

 

 

 

control

 

 

 

 

14

4

ON

OFF

 

 

 

 

 

 

 

 

 

 

15

5

ON

OFF

 

 

 

 

 

16

6

ON

OFF

 

 

 

 

 

17

7

ON

OFF

 

 

 

 

 

18

8

ON

OFF

 

Fig. 6

 

 

 

19

9

ON

OFF

 

 

 

 

 

 

 

 

 

20

0

OFF

ON

 

 

 

 

 

21

1

OFF

ON

 

 

 

 

 

22

2

OFF

ON

 

 

 

 

 

23

3

OFF

ON

 

 

 

 

 

24

4

OFF

ON

 

 

 

 

 

25

5

OFF

ON

 

 

 

 

 

26

6

OFF

ON

 

 

 

 

 

27

7

OFF

ON

 

 

 

 

 

28

8

OFF

ON

 

 

 

 

 

29

9

OFF

ON

 

 

 

 

 

30

0

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

SM831148

2

II-11

Page 117
Image 117
Sanyo TH3672R / CH3672R, XH4272R / C4272R, UH2672R, XH2672R, XH3672R Method of System Address Setting, Example of wiring