1. Specifications

Reference diagram for air-discharge chamber (field supply)

For outdoor unit C(H)2672R / 3072R / 3672R / 4272R

Required space around outdoor unit

If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.

If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation

39-3/8

Min. 7-7/8

Min.

 

Unit: inch

The top and both sides must remain open. If there are obstacles to the front and rear of

CAUTION the outdoor unit, the obstacle at either the front or rear must be no taller than the height of the outdoor unit.

(2)Multiple-unit installation Installation in lateral rows

More than 11-13/16

More than 11-13/16

than 15-3/4

More

More than 7-7/8

 

 

 

 

 

Unit: inch

CAUTION

The front and top must remain open.

The obstacles must be no taller than the height of the outdoor unit.

 

Installation in front-rear rows

 

Installation with intakes facing outlets

Installation with intakes facing

 

intakes or outlets facing outlets

More than 15-3/4

 

More than 59-1/16

More than 78-3/4

Unit: inch

CAUTION

The front and both sides must remain open.

 

 

SM831148

1

I-93

Page 97
Image 97
Sanyo KHH2672R / CH2672R, XH4272R / C4272R, UH2672R, XH2672R, UH3672R / CH3672R, XH3672R Front and both sides must remain open