Models: KH3072R / C3072R C4272R UH2672R / CH2672R UH2672R KH3672R / CH3672R TH2672R / CH2672R XH2672R / CH2672R UH3672R XH2672R / C2672R UH2672R / C2672R KHH2672R / CH2672R CH4272R TH3672R / CH3672R TH2672R / C2672R XH4272R / C4272R TH2672R THH2672R / CH2672R XH3672R / C3672R UH3672R / CH3672R XH2672R KH3672R / C3672R KH2672R / C2672R TH3672R / C3672R TH4272R / C4272R XH4272R / CH4272R KH2672R / CH2672R TH3672R TH4272R / CH4272R KH3072R / CH3072R THH3672R / CH3672R UH3672R / C3672R XH3672R / CH3672R XH3672R

1 180
Download 180 pages 17.39 Kb
Page 91
Image 91

Table 1-2 Tubing Data for Models

 

 

Models

Tubing Data

 

 

Tubing size

Liquid tube

in. (mm)

outer diameter

Gas tube

in. (mm)

Limit of tubing length

 

(ft.)

Limit of elevation

Outdoor unit is placed

higher

(ft.)

difference between

Outdoor unit is placed

the 2 units

lower

(ft.)

 

Max. allowable tubing length at shipment (ft.)

Required additional refrigerant *1

(oz./ft.)

Refrigerant charged at shipment

(lbs.)

 

 

1. Specifications

C(H)2672R

C(H)3072R

C(H)4272R

C(H)3672R

 

 

3/8 (9.52)

3/8 (9.52)

3/8 (9.52)

5/8 (15.88)

5/8 (15.88)

5/8 (15.88)

165

165

165

100

100

100

50

50

50

10 – 100

10 – 100

10 – 100

a) 0.43

b) 0.43

b) 0.43

4.2

6.2

7.9

No additional charge of compressor oil is necessary.

*1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft.

Table 1-3 List of Connection Tube Sizes

 

Main tubing (L)

 

 

Type capacity of indoor units

26 – 42

 

 

Gas tube

ø5/8"

Liquid tube

ø3/8"

Amount of additional charge per 1 ft.

0.43 oz.

 

 

SM831148