Table 1-2 Tubing Data for Models

 

 

Models

Tubing Data

 

 

Tubing size

Liquid tube

in. (mm)

outer diameter

Gas tube

in. (mm)

Limit of tubing length

 

(ft.)

Limit of elevation

Outdoor unit is placed

higher

(ft.)

difference between

Outdoor unit is placed

the 2 units

lower

(ft.)

 

Max. allowable tubing length at shipment (ft.)

Required additional refrigerant *1

(oz./ft.)

Refrigerant charged at shipment

(lbs.)

 

 

1. Specifications

C(H)2672R

C(H)3072R

C(H)4272R

C(H)3672R

 

 

3/8 (9.52)

3/8 (9.52)

3/8 (9.52)

5/8 (15.88)

5/8 (15.88)

5/8 (15.88)

165

165

165

100

100

100

50

50

50

10 – 100

10 – 100

10 – 100

a) 0.43

b) 0.43

b) 0.43

4.2

6.2

7.9

No additional charge of compressor oil is necessary.

*1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft.

Table 1-3 List of Connection Tube Sizes

 

Main tubing (L)

 

 

Type capacity of indoor units

26 – 42

 

 

Gas tube

ø5/8"

Liquid tube

ø3/8"

Amount of additional charge per 1 ft.

0.43 oz.

 

 