Sanyo UH3672R / CH3672R, UH2672R Electrical Wiring, General Precautions on Wiring, Outdoor Unit

Models: KH3072R / C3072R C4272R UH2672R / CH2672R UH2672R KH3672R / CH3672R TH2672R / CH2672R XH2672R / CH2672R UH3672R XH2672R / C2672R UH2672R / C2672R KHH2672R / CH2672R CH4272R TH3672R / CH3672R TH2672R / C2672R XH4272R / C4272R TH2672R THH2672R / CH2672R XH3672R / C3672R UH3672R / CH3672R XH2672R KH3672R / C3672R KH2672R / C2672R TH3672R / C3672R TH4272R / C4272R XH4272R / CH4272R KH2672R / CH2672R TH3672R TH4272R / CH4272R KH3072R / CH3072R THH3672R / CH3672R UH3672R / C3672R XH3672R / CH3672R XH3672R

1 180
Download 180 pages 17.39 Kb
Page 102
Image 102

1

1-12 Electrical Wiring

General Precautions on Wiring

1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.

2)Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.

3)To prevent possible hazards from insulation failure, the unit must be grounded.

4)Each wiring connection must be done in accordance with the wiring system diagram.

Wrong wiring may cause the unit to misoperate or become damaged.

5)Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.

6)Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.

1. Specifications

7)To prevent possible hazards from insulation failure, the unit must be grounded.

8)To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:

The remote control wiring and the inter-unit control wiring should be wired apart from the inter- unit power wiring.

Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.

9)If the power supply cord of this appliance is dam- aged, it must be replaced by a repair shop appointed by the manufacturer, because specialpurpose tools are required.

10)All wiring used must be Class 1.

Recommended Wire Length and Wire Diameter for Power Supply System

You must follow LOCAL ELECTRICAL CODES for wiring.

Outdoor Unit

 

 

 

 

* AWG = American Wire Gauge

 

(A) Power Supply

Trade Size

MOP

Power Supply Terminal Base

Trade Size

Model Name

(Fuse or HACR

of Conduit

 

 

of Conduit

 

 

type circuit breaker)

Capacity

Max. Wire Diameter

 

 

 

 

 

 

 

CH2672R

AWG #12

3/4 in.

30 A

50 A

AWG #6

1-1/4 in.

Max. length 64 ft.

 

 

 

 

 

 

CH3072R

AWG #10

3/4 in.

35 A (230/208 V)

50 A

AWG #6

1-1/4 in.

Max. length 92 ft.

 

 

 

 

 

 

CH3672R

AWG #10

3/4 in.

35 A (230/208 V)

50 A

AWG #6

1-1/4 in.

Max. length 92 ft.

 

 

 

 

 

 

CH4272R

AWG #10

3/4 in.

40 A

50 A

AWG #6

1-1/4 in.

Max. length 81 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(A) Power Supply

Trade Size

MOP

Power Supply Terminal Base

Trade Size

Model Name

(Fuse or HACR

 

 

of Conduit

type circuit breaker)

Capacity

Max. Wire Diameter

of Conduit

 

 

 

 

 

 

 

C2672R

AWG #12

3/4 in.

25 A

50 A

AWG #6

1-1/4 in.

Max. length 76 ft.

 

 

 

 

 

 

C3072R

AWG #10

3/4 in.

30 A (230/208 V)

50 A

AWG #6

1-1/4 in.

Max. length 99 ft.

 

 

 

 

 

 

C3672R

AWG #10

3/4 in.

30 A (230/208 V)

50 A

AWG #6

1-1/4 in.

Max. length 99 ft.

 

 

 

 

 

 

C4272R

AWG #10

3/4 in.

35 A

50 A

AWG #6

1-1/4 in.

Max. length 81 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

SM831148

I-98

Page 102
Image 102
Sanyo UH3672R / CH3672R, XH4272R / C4272R Electrical Wiring, General Precautions on Wiring, Outdoor Unit, Power Supply