1-12 Electrical Wiring
General Precautions on Wiring
1)Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
2)Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.
3)To prevent possible hazards from insulation failure, the unit must be grounded.
4)Each wiring connection must be done in accordance with the wiring system diagram.
Wrong wiring may cause the unit to misoperate or become damaged.
5)Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
6)Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
1. Specifications
7)To prevent possible hazards from insulation failure, the unit must be grounded.
8)To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the
Use shielded wires for
9)If the power supply cord of this appliance is dam- aged, it must be replaced by a repair shop appointed by the manufacturer, because specialpurpose tools are required.
10)All wiring used must be Class 1.
Recommended Wire Length and Wire Diameter for Power Supply System
You must follow LOCAL ELECTRICAL CODES for wiring.
Outdoor Unit |
|
|
|
| * AWG = American Wire Gauge | ||
| (A) Power Supply | Trade Size | MOP | Power Supply Terminal Base | Trade Size | ||
Model Name | (Fuse or HACR | ||||||
of Conduit |
|
| of Conduit | ||||
|
| type circuit breaker) | Capacity | Max. Wire Diameter | |||
|
|
|
|
|
|
| |
CH2672R | AWG #12 | 3/4 in. | 30 A | 50 A | AWG #6 | ||
Max. length 64 ft. | |||||||
|
|
|
|
|
| ||
CH3072R | AWG #10 | 3/4 in. | 35 A (230/208 V) | 50 A | AWG #6 | ||
Max. length 92 ft. | |||||||
|
|
|
|
|
| ||
CH3672R | AWG #10 | 3/4 in. | 35 A (230/208 V) | 50 A | AWG #6 | ||
Max. length 92 ft. | |||||||
|
|
|
|
|
| ||
CH4272R | AWG #10 | 3/4 in. | 40 A | 50 A | AWG #6 | ||
Max. length 81 ft. | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
| (A) Power Supply | Trade Size | MOP | Power Supply Terminal Base | Trade Size | ||
Model Name | (Fuse or HACR | ||||||
|
| of Conduit | type circuit breaker) | Capacity | Max. Wire Diameter | of Conduit | |
|
|
|
|
|
|
| |
C2672R | AWG #12 | 3/4 in. | 25 A | 50 A | AWG #6 | ||
Max. length 76 ft. | |||||||
|
|
|
|
|
| ||
C3072R | AWG #10 | 3/4 in. | 30 A (230/208 V) | 50 A | AWG #6 | ||
Max. length 99 ft. | |||||||
|
|
|
|
|
| ||
C3672R | AWG #10 | 3/4 in. | 30 A (230/208 V) | 50 A | AWG #6 | ||
Max. length 99 ft. | |||||||
|
|
|
|
|
| ||
C4272R | AWG #10 | 3/4 in. | 35 A | 50 A | AWG #6 | ||
Max. length 81 ft. | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|