4. Service procedures

Remote

Alarm

 

 

 

controller

Judgment condition

Clear condition

Judgment and correction

contents

alarm display

 

 

 

 

 

 

 

 

 

 

 

 

F31

EEPROM trouble

Reading/writing failure

Recovery at power

1. Check EEPROM (IC007).

 

 

 

reset

2. Check outdoor unit control

 

 

 

 

PCB.

 

 

 

 

 

L02

Mismatch of indoor

Indoor unit judges that type

Recovery at power

1. Check indoor unit EEPROM.

 

and outdoor unit types

does not match outdoor unit

reset

2. Check indoor unit control

 

(Espacio, Multi )

type.

 

PCB.

 

 

 

 

 

L04

Settings failure

Duplicated outdoor unit

Automatic recovery

1. Check outdoor unit

 

 

address (system address)

 

system address.

 

 

 

 

2. Check inter-unit control

 

 

 

 

wiring.

 

 

 

 

 

L07

Settings failure

Group control wiring is

Recovery at power

1. Check inter-unit control

 

 

connected to an

reset

wiring.

 

 

independent-control indoor

 

2. Check indoor unit

 

 

 

 

EEPROM.

 

 

 

 

 

L10

Settings failure

Outdoor unit capacity not set.

Recovery at power

Check outdoor unit EEPROM.

 

 

 

reset

 

L13

Indoor-outdoor unit

Outdoor unit judges that type

Recovery at power

1. Check indoor unit

 

types

does not match indoor unit

reset

EEPROM.

 

 

type.

 

2. Check outdoor unit control

 

 

 

 

PCB.

 

 

 

 

 

E06

Outdoor unit detected

Serial signal receiving failure

Automatic

1. Check inter-unit control

 

abnormal signal from

(including failure to verify No.

recovery

wiring.

 

indoor unit.

of units)

 

2. Check outdoor unit

 

 

 

 

 

E07

Outdoor unit sending

Serial signal sending failure

Automatic

1. Check inter-unit control

 

failure to indoor unit

 

recovery

wiring.

 

 

 

 

2. Check outdoor unit control

 

 

 

 

PCB.

E14

Settings failure

Duplicated master unit in

Recovery at power

1. Check inter-unit control

 

 

simultaneous-operation multi

reset

wiring.

 

 

control

 

2. Check indoor unit

 

 

(Detected by outdoor unit)

 

combination.

 

 

 

 

 

E15

Automatic address

Indoor unit capacity too low.

Recovery at power

1. Check inter-unit control

 

setting failure

 

reset

wiring.

 

 

 

 

2. Check outdoor unit control

 

 

 

 

PCB.

 

 

 

 

 

E16

Automatic address

Indoor unit capacity too high.

Recovery at power

1. Check inter-unit control

 

setting failure

 

reset

wiring.

 

 

 

 

2. Check outdoor unit control

 

 

 

 

PCB.

 

 

 

 

 

E20

Automatic address

Outdoor unit cannot receive

Recovery at power

1. Check inter-unit control

 

setting failure

any serial signals from indoor

reset

wiring.

 

 

units.

 

2. Check outdoor unit control

 

 

 

 

PCB.

 

 

 

 

 

E31

Communications

No communication possible

Automatic recovery

Check outdoor unit control

 

trouble within unit

with MDC for 3 minutes or

 

PCB.

 

 

longer.

 

 

 

 

 

 

 

H01

Overcurrent

Inverter stops after alarm is

Recovery at restart

1. Refrigerant cycle trouble,

 

 

detected.

 

overload operation

 

 

 

 

2. Loose screws between HIC

 

 

 

 

control PCB and radiating

 

 

 

 

plate

 

 

 

 

3. Cooling failure of radiating

 

 

 

 

plate

 

 

 

 

4. Check outdoor unit PCB

 

 

 

 

wiring.

 

 

 

 

 

 

 

 

 

 