4. Service procedures
Remote | Alarm |
|
|
| |
controller | Judgment condition | Clear condition | Judgment and correction | ||
contents | |||||
alarm display |
|
|
| ||
|
|
|
| ||
|
|
|
|
| |
F31 | EEPROM trouble | Reading/writing failure | Recovery at power | 1. Check EEPROM (IC007). | |
|
|
| reset | 2. Check outdoor unit control | |
|
|
|
| PCB. | |
|
|
|
|
| |
L02 | Mismatch of indoor | Indoor unit judges that type | Recovery at power | 1. Check indoor unit EEPROM. | |
| and outdoor unit types | does not match outdoor unit | reset | 2. Check indoor unit control | |
| (Espacio, Multi ) | type. |
| PCB. | |
|
|
|
|
| |
L04 | Settings failure | Duplicated outdoor unit | Automatic recovery | 1. Check outdoor unit | |
|
| address (system address) |
| system address. | |
|
|
|
| 2. Check | |
|
|
|
| wiring. | |
|
|
|
|
| |
L07 | Settings failure | Group control wiring is | Recovery at power | 1. Check | |
|
| connected to an | reset | wiring. | |
|
|
| 2. Check indoor unit | ||
|
|
|
| EEPROM. | |
|
|
|
|
| |
L10 | Settings failure | Outdoor unit capacity not set. | Recovery at power | Check outdoor unit EEPROM. | |
|
|
| reset |
| |
L13 | Outdoor unit judges that type | Recovery at power | 1. Check indoor unit | ||
| types | does not match indoor unit | reset | EEPROM. | |
|
| type. |
| 2. Check outdoor unit control | |
|
|
|
| PCB. | |
|
|
|
|
| |
E06 | Outdoor unit detected | Serial signal receiving failure | Automatic | 1. Check | |
| abnormal signal from | (including failure to verify No. | recovery | wiring. | |
| indoor unit. | of units) |
| 2. Check outdoor unit | |
|
|
|
|
| |
E07 | Outdoor unit sending | Serial signal sending failure | Automatic | 1. Check | |
| failure to indoor unit |
| recovery | wiring. | |
|
|
|
| 2. Check outdoor unit control | |
|
|
|
| PCB. | |
E14 | Settings failure | Duplicated master unit in | Recovery at power | 1. Check | |
|
| reset | wiring. | ||
|
| control |
| 2. Check indoor unit | |
|
| (Detected by outdoor unit) |
| combination. | |
|
|
|
|
| |
E15 | Automatic address | Indoor unit capacity too low. | Recovery at power | 1. Check | |
| setting failure |
| reset | wiring. | |
|
|
|
| 2. Check outdoor unit control | |
|
|
|
| PCB. | |
|
|
|
|
| |
E16 | Automatic address | Indoor unit capacity too high. | Recovery at power | 1. Check | |
| setting failure |
| reset | wiring. | |
|
|
|
| 2. Check outdoor unit control | |
|
|
|
| PCB. | |
|
|
|
|
| |
E20 | Automatic address | Outdoor unit cannot receive | Recovery at power | 1. Check | |
| setting failure | any serial signals from indoor | reset | wiring. | |
|
| units. |
| 2. Check outdoor unit control | |
|
|
|
| PCB. | |
|
|
|
|
| |
E31 | Communications | No communication possible | Automatic recovery | Check outdoor unit control | |
| trouble within unit | with MDC for 3 minutes or |
| PCB. | |
|
| longer. |
|
| |
|
|
|
|
| |
H01 | Overcurrent | Inverter stops after alarm is | Recovery at restart | 1. Refrigerant cycle trouble, | |
|
| detected. |
| overload operation | |
|
|
|
| 2. Loose screws between HIC | |
|
|
|
| control PCB and radiating | |
|
|
|
| plate | |
|
|
|
| 3. Cooling failure of radiating | |
|
|
|
| plate | |
|
|
|
| 4. Check outdoor unit PCB | |
|
|
|
| wiring. | |
|
|
|
|
| |
|
|
|
|
|